Moxa C Programmable RTU Controllers Module Specifications and Wiring
16-channel Digital Output Module
-2600-T: 16 digital outputs, 24 VDC, sink type, 0.2 A
16 channels, 24 VDC, sink type
120m ohms (typical)
-state Resistance: 500K ohms (typical)
200 mA per channel
I/O to logic (photocoupler isolation)
-to-Channel Isolation: 2.5K VDC
ing Temperature: -40 to 75°C
Power Consumption: 24 mA @ 24 VDC (typical)
AWG 14 (2.0 mm x mm) max.
8-channel Analog Input Module, 16-bit Resolution
RM-3802-T: 8 analog inputs, 4 to 20 mA, 16 bits
8 channels, differential
4 to 20 mA
120 ohms
16 bits, 0.24 μA/bit
-40°C, 75°C
All channels: 12 samples/sec
Per channel: 1.5 samples/sec
200 mA per channel
I/O to logic (photocoupler isolation)
nnel-to-Channel Isolation: 2.5K VDC
-40 to 75°C
Power Consumption: 30 mA @ 24 VDC (typical)
AWG 14 (2.0 mm x mm) max.