
Industrial Ethernet Gateway Selection Guide
CP-602 Series
2-port CAN interface with 2 KV isolation
• PCIe, universal PCI, and PCI/104-Plus
interfaces available
• Wide temperature available for -40 to 85ºC
environments
• 2 KV optical isolation protection
ICF-1180I Series
PROFIBUS to Fiber Converter
• Automatic baud rate detection
• Redundant power input
• Hardware fail safe prevents corrupted
datagrams in functioning segment
• 2 KV optical isolation protection
5 6
Modbus RTU/ASCII
to Modbus TCP
DF1 to EtherNet/IP
Modbus RTU/ASCII
to PROFIBUS
Model
MB3180
MB3280
MB3480
MB3170
MB3170I
MB3270
MB3270I
EIP3170
EIP3170I
EIP3270
EIP3270I
4101-MB-PBS
4101I-MB-PBS
Ethernet Interface
Number of Ports
1 2 (1 IP) 2 (2 IPs) -
Speed
10/100 Mbps -
Connector
RJ45 -
Magnetic Isolation Protection
1.5 KV -
Serial Interface
Number of Ports
1/2/4 1 2 1 2 1
Serial Standards
RS-232/422/485 RS-232/422/485 RS-232/422 RS-232/422/485
RS-232 Connectors
DB9-M DB9-M DB9-M DB9-M DB9-M DB9-M
RS-422/485 Connectors
DB9-M Terminal Block DB9-M Terminal Block DB9-M DB9-M
ESD Protection
15 KV
RS-485 Data Direction Control
ADDC®
Serial Communication
Parameters
Data Bits: 7, 8; Stop Bits: 1, 2
Parity
None, Even, Odd, Space, Mark
Flow Control
RTS/CTS, DTR/DSR (RS-232 only) RTS/CTS, DTR/DSR RTS/CTS
Baudrate
50 bps to 921.6 Kbps 1200 bps to 921.6 Kbps 50 bps to 921.6 Kbps
Isolation
–
✔
(I Model only)
Software
Utilities
MGate Manager Suite for Windows 98/ME/NT/2000, Windows XP/2003/Vista/2008/7 x86/x64
Smart Routing ✔ ✔ ✔ ✔ ✔
–
Serial Redirection
– –
✔
–
✔
–
ProCOM
–
✔ ✔ ✔ ✔
–
Priority Control
–
✔ ✔
– – –
QuickLink
– – – – –
✔
PROFIBUS
– – – – – DP-V0 Slave
Ethernet Protocol
Modbus TCP Modbus TCP CIP (PCCC) on Ethernet/IP –
Serial Protocol
Modbus RTU/ASCII DF1 Full-duplex Modbus RTU/ASCII
Physical Characteristics
Housing
Metal Plastic Plastic Metal
Environmental Limits
Operating Temperature
0 to 55°C 0 to 55°C or -40 to 75°C (-T Model) 0 to 60°C or -40 to 75°C (-T model)
Power Requirements
Input Voltage
12 to 48 VDC
Standards and Certifications
Safety
UL 60950-1, EN 60950-1
Hazardous Location
– UL/cUL Class I Division 2 Groups A/B/C/D, ATEX Zone 2 -
EMC
CE, FCC
EMI
EN 55022 Class A, FCC Part 15 Subpart B Class A
EMS
EN 55024,
EN61000-4-2 (ESD) Level 2,
EN61000-4-3 (RS) Level 2,
EN61000-4-4 (EFT) Level 2,
EN61000-4-5 (Surge) Level 2,
EN61000-4-6 (CS) Level 2,
EN61000-4-8,
EN61000-4-11,
EN61000-4-12
EN 55024,
EN 61000-4-2 (ESD) Level 3,
EN 61000-4-3 (RS) Level 3,
EN 61000-4-4 (EFT) Level 4,
EN 61000-4-5 (Surge) Level 3,
EN 61000-4-6 (CS) Level 3,
EN 61000-4-8,
EN 61000-4-11,
EN 61000-4-12
Marine
– DNV – –
Reliability
Warranty
5 years (see www.moxa.com/warranty)
More Industrial Ethernet Gateway Solution to Choose From:
Kommentare zu diesen Handbüchern